Substation energy imbalance: where it comes from and how to find where energy is lost
The substation imbalance is the difference between the energy supplied at the input and the sum metered at consumers. The metering system reports it as one number per substation. But one number hides different causes, and each is fixed differently. GRID-IN splits the imbalance by cause and takes it down to addresses.
What makes up the imbalance?
| Cause | What to do about it |
|---|---|
| Technical losses | always present; calculate them from the network diagram and reduce them by network work: phase rebalancing, replacing overloaded sections |
| Unmetered consumption (theft) | a visit to the address, a report, back-billing |
| Unauthorised consumption | a visit, then a contract or disconnection |
| Faulty meter | meter replacement or repair |
| Meter not reporting | restore communication; until then its consumption looks like losses |
| Meter assigned to the wrong substation | fix the balance group membership in the records |
| Error in the metering registry | fix the record; no visit needed |
Why is the imbalance percentage not enough?
The same 13 % can mean one large consumer bypassing the meter, an error in the metering registry, or a long overloaded line. The first needs a visit to an address, the second a registry fix, the third network work. Until the cause is named, a visit is a guess.
What does a negative imbalance mean?
Consumers “used” more than was supplied at the input. Energy does not appear from nowhere, so this is a metering error, not losses. Such an imbalance means fixing the metering first and only then looking for losses.
What does GRID-IN do?
- reports for every substation whether there is enough data for a conclusion and what is wrong with it;
- detects non-technical losses with several independent methods;
- calculates the technical losses of every section from the network diagram;
- merges the findings into one target list with address, type of irregularity, energy estimate and confirmation probability.
The substation imbalance ends up split into technical losses, specific addresses and metering errors. More — Energy theft, Meters of another substation, Technical losses.
What imbalance is normal?
There is no single number: the acceptable level depends on line length and cross-section, load and meter accuracy class. So compare the imbalance not with a norm but with the calculated technical losses of that substation. Everything above them and above metering accuracy is non-technical losses or metering errors. An imbalance “within the norm” does not mean there is no theft: it can hide behind low technical losses.
What is needed?
Load profiles of consumer meters and of the substation input meter for the same period. To split technical from non-technical losses — the 0.4 kV network diagram. Details — Data requirements.