Consumer phase identification: why it matters which phase a meter is on

A 0.4 kV network is three-phase, while most consumers are connected to a single phase. Which one is usually not recorded in diagrams or line documentation. Without it, losses cannot be calculated accurately and phase loads cannot be balanced.

Why does phasing matter?

Illustrative example. A line with a total current of 60 A. Split evenly — 20 A per phase, the neutral current is close to zero. With 40 A on one phase and 10 A on each of the other two, about 30 A flows in the neutral, and line losses are noticeably higher for the same energy delivered.

Why can phasing not simply be found by trial?

A three-phase meter can be connected to the three network phases in six ways. For two meters there are already 6 × 6 = 36 options, for N meters — 6N. Even for 15 meters on one line, trying all options would take many days, and a substation can have dozens or hundreds of meters. Checking on site means walking to every connection.

What does GRID-IN do?

GRID-IN determines consumer phasing from AMI data and the network diagram, without a site walk, and uses it in a per-phase network calculation: currents and losses in the phases and in the neutral, load unbalance, consumer voltages. This shows where phase loads are uneven and which consumers are worth moving to another phase.

What is needed?

Load profiles of the substation input meter and of three-phase consumer meters — per phase (L1, L2, L3), not only as a total; a single-line network diagram. Details — Data requirements and Technical loss calculation.